Many professionals working on UL certification for electrical switches are curious about the test requirements for UL61058 certification. JJR Laboratory in China, an independent UL-authorized testing and certification organization, is well-versed in UL standards and certification processes for electrical switches. Below is an introduction to the UL61058 certification test requirements for electrical switches.
1. Test Samples
- Three samples are required, and they must be tested simultaneously.
2. Adequate Test Circuits
- Some switch designs require two or more test circuits depending on the declared application of the switch.
3. Lab Power System Wiring Diagram
- Includes details about the power source (live/neutral/ground wires), overcurrent protectors, and branches.
4. Lab Layout Diagram
- Should specify the positions of all equipment, such as power sources, overload devices, endurance, temperature rise, and dielectric strength testing devices.
5. Test Circuit Wiring Diagram
- Includes details of the power source (live/neutral/ground wires), the test switch, passive loads, grounding fuses (Dead Metal Fuse), counters, etc.
6. Grounding Fuse (Dead Metal Fuse)
- This fuse is connected to the metallic shell of the switch or its mounting fixture. It must be UL-recognized, with a maximum rated current not exceeding 15A and a minimum voltage equal to or greater than the rated voltage of the switch.
7. Counter
- Counts one cycle every time the test current flows through the switch.
8. Automatic Stop
- The test setup must stop automatically in the event of contact fusion, grounding fuse burnout, or other test failures.
1. AC Power Requirements
- The “live” and “neutral/ground” sides must be explicitly marked.
2. DC Power Requirements
- The “+” and “-” sides must be clearly marked.
3. Voltage Requirements
- \( V_r \leq V_c \leq 1.05 \, V_r \) (where \( V_c \) is the closed-circuit voltage and \( V_r \) is the rated voltage of the switch).
- \( V_o \leq 1.1 \, V_c \) (where \( V_o \) is the open-circuit voltage).
4. Frequency Requirements
- For switches rated at 50/60 Hz, the test frequency is 50 Hz.
- For switches rated at 60 Hz, the test frequency is 60 Hz.
- For switches rated at 50 Hz, the test frequency is 50 Hz.
5. DC Ripple
- The peak-to-peak ripple voltage must not exceed 5% of the DC voltage.
1. Load Characteristics
- Examples include resistive, inductive, motor loads, or tungsten filament lamps, depending on the declared switch application.
2. AC Load Waveform
- Must be a pure sine wave without distortion or deformation.
3. Inductor Parallel Resistor
- If a hollow inductor is used with a parallel resistor in the circuit, the resistor's power dissipation must not exceed 3% of the total power.
4. Motor Load (EU Regulations)
- Current waveforms must be continuous, with no interruptions. Large waveform durations should last 50-100 ms.
1. Adequate Test Apparatus
- Three samples must be tested simultaneously.
2. Oven Requirement
- For applications exceeding 55°C, an oven must be used, maintaining temperature at \( +0/5°C \) from the set value. Airflow in the oven must not directly impact the test samples.
3. Operation Frequency
- Depending on the current:
- <10A: 15 cycles/min.
- 10A–25A: 7.5 cycles/min.
- >25A: 3.75 cycles/min.
4. ON/OFF Periods per Cycle
- ON: 25% \( (+5/0\%) \), OFF: 75% \( (+5/0\%) \).
- <10A: 1 sec ON, 3 sec OFF.
- 10A–25A: 2 sec ON, 6 sec OFF.
- >25A: 4 sec ON, 12 sec OFF.
5. Speed Requirements
- Mechanical Switches:
- Slow speed: Linear: 20 mm/s; Rotation: ≤45°: 9°/s, >45°: 18°/s.
- Accelerated speed: Linear: 80 mm/s; Rotation: ≤45°: 45°/s, >45°: 90°/s.
- Electronic Switches:
- Accelerated speed: Linear: 25 mm/s; Rotation: 45°/s.
1. Environment
- Ensure the test area is not affected by wind or thermal conductors to avoid skewing results.
2. Thermocouples
- Preferably Type J; K or T is also acceptable, with wire gauges of 28–32 AWG.
3. Temperature Measuring Instruments
- Channels must be calibrated and specified for use with the designated thermocouple type (J, K, or T).
1. Adequate Test Range Validation
- Ensure the equipment covers the necessary range.
2. Test Duration
- The dielectric test must last at least 60 seconds.
The collaboration between telematics and vehicle drive recorders;Benefits of combining drive recorders and telematics;Principles of telematics and drive recorders
How to Achieve Compliance with the EU EN55032 Stan
EU EN301908 Standard for Mobile Communication Prod
What is the Vacuum Cleaner CSA C22.2 No.243 Test R
UL 982 Report Mandatory Enforcement on August 30,
Amazon Compliance for Lithium Battery-Powered Home
Guide to Compliance Certification for Projector Ex
US Clothing 16 CFR 1610 Flammability Test + GCC +
Amazon US Button Cell Battery UL 4200A + 16 CFR 12
24-hour online customer service at any time to respond, so that you worry!